Comparison of water consumption between closed cooling tower and open cooling tower

Author:Trlon  Views:  Time:2021-07-26
Comparison of water consumption between closed cooling tower and open cooling tower

  China trlon air conditioner provides cooling tower water consumption data information with the following calculation formulas:TRMCooling tower noise reduction treatment manufacturer

  Closed cooling tower spray water loss:TRMCooling tower noise reduction treatment manufacturer

  is calculated based on 300m⊃3;/h, 37℃-32℃ cooling capacity, spraying water flow rate is 270m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

  Drifting rate: 0.001% of spraying water flow, water consumption per hour is 0.0027m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

  Evaporation rate: 0.8% of spray water flow, water consumption per hour 2.16m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

  Internal circulating water loss: Determined according to the pipeline installation, if the internal pipeline does not seepage or leaks, it can be regarded as not calculated.TRMCooling tower noise reduction treatment manufacturer

  The total water consumption per hour is 2.1627m⊃3;/h, and it operates at full load for 24 hours a day, and the average daily water consumption is 51.9m⊃3;/h. It is calculated based on the three seasons of operation in spring, autumn and summer in the whole year, and closed in winter. The detailed table is below.TRMCooling tower noise reduction treatment manufacturer

  Open cooling tower spray water loss:TRMCooling tower noise reduction treatment manufacturer

  is calculated based on 300m⊃3;/h, 37℃-32℃ cooling capacity, spraying water flow rate is 300m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

  Drifting rate: 0.3% of spraying water flow, water consumption per hour 0.9m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

  Evaporation rate: 0.8% of spray water flow, water consumption per hour 2.4m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

  The total water consumption per hour is 3.3m⊃3;/h, operating at full load for 24 hours a day, the average daily water consumption is 79.2m⊃3;/h, in which the cost loss and the loss of potion, softener, and pipelines Time-consuming maintenance caused by blocking. It is calculated based on the three seasons of operation in spring, autumn and summer in the whole year, and closed in winter. The detailed table is below.TRMCooling tower noise reduction treatment manufacturer

   

Closed cooling tower, spray pump water volume270m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Open cooling tower, circulating water volume:300m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Spring and summerTRMCooling tower noise reduction treatment manufacturer

Drift rateTRMCooling tower noise reduction treatment manufacturer

0.001%,Water consumption per hour0.001%*270(m⊃3;/h)=0.0027m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

0.3%,Water consumption per hour 0.3%*300(m⊃3;/h)TRMCooling tower noise reduction treatment manufacturer

=0.9m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Water consumption0.0027m⊃3;/h*24(hour)*270(day)=23.328m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Water consumption0.9m⊃3;/h*24(hour)*270(day)TRMCooling tower noise reduction treatment manufacturer

=5832m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

EvaporationTRMCooling tower noise reduction treatment manufacturer

0.8%,Water consumption0.8%*270(m⊃3;/h)=2.16m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

0.8%,Water consumption0.8%*300(m⊃3;/h)=2.4m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Water consumption2.16m⊃3;/h*24(day)*270(sky)=13996m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Water consumption2.4m⊃3;/h*24(hour)*270(day)=15552m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

Winter seasonTRMCooling tower noise reduction treatment manufacturer

Drift rateTRMCooling tower noise reduction treatment manufacturer

The spray pump can be turned off, about 0TRMCooling tower noise reduction treatment manufacturer

Water consumption 0.9m⊃3;/h*24(hour)*90(day)TRMCooling tower noise reduction treatment manufacturer
TRMCooling tower noise reduction treatment manufacturer
=1944m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

 

EvaporationTRMCooling tower noise reduction treatment manufacturer

The spray pump can be turned off, about 0TRMCooling tower noise reduction treatment manufacturer

Water consumption2.4m⊃3;/h*24(Hour)*90 (day)TRMCooling tower noise reduction treatment manufacturer

=5184m⊃3;/hTRMCooling tower noise reduction treatment manufacturer

annualTRMCooling tower noise reduction treatment manufacturer

Total water consumptionTRMCooling tower noise reduction treatment manufacturer

About 14000m⊃3; (directly consumed by tap water)TRMCooling tower noise reduction treatment manufacturer

About 28512m⊃3; (The water consumption is the consumption of the circulating aqueous solution containing the medicine and the demineralized water)TRMCooling tower noise reduction treatment manufacturer

Article Address:https://www.trlen.com/baike/472.html

News

Contact

Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.

Contact:Mr. Wang

Free Hotline:4008-8383-95

Company Email:sales@trlon.com

Web Site:https://www.trlen.com/

Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen

Trlon WechatClose
alibaba