Trlon air conditioner manufacturers have silent cooling towers, closed cooling towers and cooling tower noise reduction, maintenance and transformation services.
National Service Hotline National Service Hotline:

4008-8383-95

Your current location:HOME > News > FAQ

FAQ

Cooling tower maintenance and site setting method

Author:Trlon  Views:  Time:2021-02-24
Cooling tower maintenance and site setting method

  Regarding maintenance:

  1) The V-belt of the blower may be slightly stretched during the first operation. Please adjust the belt tightness according to the adjustment method. If it is tightened too tightly, the bearing will be damaged and an accident may occur.EjTCooling tower noise reduction treatment manufacturer

  2) Please clean the drain hole of the upper tank and the filter of the lower tank regularly once a month.EjTCooling tower noise reduction treatment manufacturer

  3) Please loosen the belt, add oil to the blower bearing part, and cover the motor when it is off. During the initial operation, determine the tightness of the belt, tighten the nut, and add oil to the bearing of the blower. In addition, confirm whether there is a bird's nest or foreign matter in the tower, and then start the operation.EjTCooling tower noise reduction treatment manufacturer

  4) Exchange circulating water at least twice a year.EjTCooling tower noise reduction treatment manufacturer

  5) After the circulating water evaporates, it will leave dissolved substances in the water, which will increase the water concentration. After the water is concentrated, the corrosiveness and scale will increase, which will reduce the cooling tower capacity and damage the piping and equipment. In order to prevent this situation, it is recommended to use a part of the circulating water to solve the problem:EjTCooling tower noise reduction treatment manufacturer

  The drain valve only opens a little during operation (please turn off the drain valve when the operation stops);EjTCooling tower noise reduction treatment manufacturer

  Clean the lower tank and change the water regularly;EjTCooling tower noise reduction treatment manufacturer

  Make the running water level rise and overflow frequently;EjTCooling tower noise reduction treatment manufacturer

  Equipped with automatic water changing device.EjTCooling tower noise reduction treatment manufacturer

  Precautions for cooling tower design and selection:EjTCooling tower noise reduction treatment manufacturer

  About setting place:

  1. The cooling tower should be installed in a ventilated place. Try to avoid places with dust, acid exhaust, high temperature exhaust, and high water vapor. Especially after inhaling a large amount of soot, not only the cooling tower but also the piping and other equipment will be corroded.EjTCooling tower noise reduction treatment manufacturer

  2. If there are obstacles or short intervals between the shutter surface and the wall, air inhalation will cause impedance, resulting in low cooling capacity, please keep the distance above:EjTCooling tower noise reduction treatment manufacturer

  Cooling capacity L size:EjTCooling tower noise reduction treatment manufacturer

  5~15RT above 0.5m;EjTCooling tower noise reduction treatment manufacturer

  20~70RT above 1.0m;EjTCooling tower noise reduction treatment manufacturer

  80~100RT above 2.0m;EjTCooling tower noise reduction treatment manufacturer

  110~175RT above 2.5m;EjTCooling tower noise reduction treatment manufacturer

  200~400RT above 3.0m;EjTCooling tower noise reduction treatment manufacturer

  Above 500RT and above 3.5m.EjTCooling tower noise reduction treatment manufacturer

  Note: If the obstacle is the outer wall and the outer wall can be opened, the L size can be adjusted appropriately according to the opening area and opening rate. In addition, according to the height of the outer wall, the L size can also be adjusted appropriately, please ask the cooling tower manufacturer.EjTCooling tower noise reduction treatment manufacturer

  3. When the obstacle is higher than the cooling tower, in order to prevent air short circuit, please use straight pipe.EjTCooling tower noise reduction treatment manufacturer

  4. Pipes according to the piping size recorded in the sample.EjTCooling tower noise reduction treatment manufacturer

  5. Please install the piping and water pump below the operating water level of the cooling tower, and do not allow air to be sucked in.EjTCooling tower noise reduction treatment manufacturer

  About heat-resistant temperature:

  The filling material is made of rigid polyvinyl chloride resin (PVC), and the inflow of high temperature water will cause deformation. In the case of the standard type, the use limit temperature is 45°C. Please pay special attention to the excessive flow and high temperature water during the trial operation. In addition, when the temperature is above 45℃, some powerful manufacturers prepare heat-resistant fillers. Please ask the cooling tower manufacturer trlon energy-saving air conditioners.EjTCooling tower noise reduction treatment manufacturer

Article Address:https://www.trlen.com/baike/319.html

News

Contact

Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.

Contact:Mr. Wang

Free Hotline:4008-8383-95

Company Email:sales@trlon.com

Web Site:https://www.trlen.com/

Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen

Trlon WechatClose
alibaba