Calculation method of water supply for air conditioning cooling tower

Author:Trlon  Views:  Time:2021-02-23
Calculation method of water supply for air conditioning cooling tower

  Water loss by evaporation (E)BgBCooling tower noise reduction treatment manufacturer

  E = Q/600 = (T1-T2)×L/600BgBCooling tower noise reduction treatment manufacturer

  E represents the amount of evaporated water (kg/h);BgBCooling tower noise reduction treatment manufacturer

  Q represents heat load (Kcal/h);BgBCooling tower noise reduction treatment manufacturer

  600 represents the latent heat of evaporation of water (Kcal/h);BgBCooling tower noise reduction treatment manufacturer

  T1 represents the water temperature (℃); T2 represents the water temperature (℃);BgBCooling tower noise reduction treatment manufacturer

  L represents the circulating water volume (kg/h).BgBCooling tower noise reduction treatment manufacturer

  Splash loss water (C): The splash loss of the cooling tower is determined by the cooling tower design type, wind speed and other factors. Under normal circumstances, its value is approximately equal to about 0.1% to 0.2% of the circulating water volume.BgBCooling tower noise reduction treatment manufacturer

  Regular discharge water loss (D): Regular discharge water loss must be determined by factors such as water quality or solid concentration in the water. Generally, it is about 0.3% of the circulating water volume.BgBCooling tower noise reduction treatment manufacturer

  M=E+C+DBgBCooling tower noise reduction treatment manufacturer

  Evaporation loss (E), splash loss (C), periodic discharge water loss (D).BgBCooling tower noise reduction treatment manufacturer

  When the cooling tower is used for air conditioning, the temperature difference is designed to be 5℃. At this time, the make-up water required by the cooling tower is about 2% of the circulating water.BgBCooling tower noise reduction treatment manufacturer

  Teling cooling tower water drift rate is 0.001%; welcome to inquire us!BgBCooling tower noise reduction treatment manufacturer

Article Address:https://www.trlen.com/baike/318.html

News

Contact

Guangdong Trlon Energy-saving Air Conditioning Equipment Co., Ltd.

Contact:Mr. Wang

Free Hotline:4008-8383-95

Company Email:sales@trlon.com

Web Site:https://www.trlen.com/

Company Address: 1916A, Block A, David Donglong Business Building, Longhua, Longhua District, Shenzhen

Trlon WechatClose
alibaba